Material
Insulation: EPR, IEC 60092-360
Sheath: SHF2, IEC 60092-360
Flame retardant: IEC 60332-3-22, Cat.A
Fire resistance: IEC 60331-21
Halogen free properties: IEC 60754-1,2 & IEC 60684-2
Low smoke properties: IEC 61034-1,2
Sunlight resistance: UL 1581
Cold properties (option): CSA C22.2 No.03 (Bending : -40C, Impact : -35C)
Oil/Mud resistance (option): NEK 606-2016 (Category a, b, c, d)
Conductor: Circular tinned stranded copper as per IEC 60228, Class 2
Conductor screen: Semi-conducting tape and Semi-conducting compound
Insulation: Halogen Free Ethylene Propylene Rubber
Insulation screen: Semi-conducting compound and Semi-conducting tape
Metallic screen: Tinned copper wire braid as per IEC 60092-354
Fire proof layer: Mica glass tape and Silicon glass tape
Cabling (with filler)
Bedding (Fire Block): Halogen free compound
Inner sheath: Halogen free thermosetting compound as per IEC 60092-360, SHF2
Armour: Tinned copper wire braid as per IEC 60092-354
FIRE RESISTANT (option): Galvanized steel wire braid as per IEC 60092-354
Outer sheath: Halogen
Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids.